Table 15 - System Dynamic Data (based on reference 5) Unit Reactance, pu Unit size Unit MVA Unit Transformer Inertia Damping group MW Type Base X=d MJ/MW Ratio --------------------------------------------------------------- U12 12 Oil/Steam 14 0.32 0.13 2.8 0.0 U20 20 Oil/CT 24 0.32 0.13 2.8 0.0 U50 50 Hydro 53 0.28 0.1 3.5 0.0 U76 76 Coal/Steam 89 0.3 0.13 3.0 0.0 U100 100 Oil/Steam 118 0.32 0.13 2.8 0.0 U155 155 Coal/Steam 182 0.3 0.13 3.0 0.0 U197 197 Oil/Steam 232 0.32 0.13 2.8 0.0 U350 350 Coal/Steam 412 0.3 0.13 3.0 0.0 U400 400 Nuclear 471 0.4 0.15 5.0 0.0 Notes: 1. A classical model is assumed for each generator. 2. Reactance and inertia data are typical of generators of the same type and the same size. 3. Reactance values are based on the given MVA base. 4. Inertia values are based on the unit size in MW.